Skip to content

The four service line categories

Lead, galvanized requiring replacement, unknown, and non-lead, and how each is decided.

Last reviewed against the sources linked in the text.

Every service line in your inventory gets one of four categories. Each side of the line (the part the system owns and the part the customer owns) has a material, and the category comes from both. (40 CFR 141.84(a)) (definitions in 40 CFR 141.2)

CategoryWhen it applies
LeadAny portion of the line is lead.
Galvanized requiring replacement (GRR)A galvanized portion that is, or ever was, downstream of lead, or sits downstream of a portion whose material is unknown. See the GRR guide.
Lead status unknownThe material hasn't been identified, and nothing found so far makes it lead or GRR.
Non-leadEvery portion is a known non-lead material, such as copper or plastic.

Lead connectors are tracked separately

Goosenecks and pigtails don't change a line's category, but the baseline inventory has to record them, and every year the system certifies that lead connectors it came across were replaced. (40 CFR 141.84(a)) (40 CFR 141.90(e)(5))

Why unknown matters

Unknown lines count toward the replacement pool until they're identified, and the people they serve get notices. (40 CFR 141.84(d)(6)) (40 CFR 141.85(e)) When an unknown line turns out to be non-lead, it comes out of the pool. That makes resolving unknowns the most valuable early work for most systems.

This guide explains the rules in plain language; it isn't legal advice. Your State's drinking water program has the final word on your system.