Skip to content

Galvanized requiring replacement, explained

Why some galvanized lines must be replaced like lead lines, and Washington's rules.

Last reviewed against the sources linked in the text.

Galvanized steel isn't lead, but the rule treats some galvanized lines like lead lines, based on what is or was upstream of them. (40 CFR 141.2)

When a galvanized line is GRR

  • It is, or ever was, downstream of a lead service line or lead portion.
  • It's downstream of a portion whose material is unknown.
  • You can't show it was never downstream of lead.

(definitions in 40 CFR 141.2)

Washington's guidance

DOH says to classify a galvanized line as GRR unless records show it was never downstream of lead. Without records, it can be non-lead only if it wasn't installed earlier than records suggest, no lead lines were found in records or field checks, and there's no record or knowledge of lead lines or their replacement. If upstream lead turns up later, tell the State within 30 days. (WA DOH 331-723)

What it means for you

GRR lines count toward the replacement pool and get the same notices as lead lines. (40 CFR 141.84(d)(6)) (40 CFR 141.85(e)) If the system side is unknown and the customer side is galvanized, identifying the system side first can change the customer side's category too.

This guide explains the rules in plain language; it isn't legal advice. Your State's drinking water program has the final word on your system.